YardLedger™

Before the first hard freeze

How to Drain a Backflow Preventer for Winter (PVB, RPZ, DC & AVB)

To drain a backflow preventer, first identify the exact manufacturer and model — not only whether it is a PVB, RPZ, double check or AVB — and follow that model's instructions: shut off and relieve the supply, open every drain path it names, and leave the valves in their specified winter positions. If anything is uncertain, arrange qualified backflow service.

A backflow assembly can retain water in its body, valves and risers. Recognizing a PVB, RPZ, double check or AVB is a first step, not a complete winterization procedure. Find the manufacturer, model and installation instructions; if any are uncertain, arrange qualified backflow service before opening parts or connecting air.

Working through it

How to Drain a Backflow Preventer for Winter (PVB, RPZ, DC & AVB): step by step. A 6-step process diagram, in order: 1. Identify the exact model, not only the device family; 2. Separate supply shutoff and pressure relief; 3. Keep air-phase isolation separate from final storage; 4. Check every required drain path and retained-water space; 5. Use only the model’s internal-service instructions; 6. Complete the specified freeze protection and final storage.
  1. Step 1

    Identify the exact model, not only the device family

    Use the representative drawings to recognize a possible device family, then read the actual model markings and obtain its freeze-protection instructions. The installation’s drain locations and air connection matter as much as the name. If you cannot verify them, use qualified backflow service.

  2. Step 2

    Separate supply shutoff and pressure relief

    Follow the model and installation instructions to close the upstream irrigation water supply and relieve pressure before opening drains or servicing the assembly. Do not work on pressurized fittings. The supply shutoff remains closed during winter; it is distinct from assembly valves that may later need a part-open storage position.

  3. Step 3

    Keep air-phase isolation separate from final storage

    A downstream air connection does not establish isolation. FEBCO 765 and Zurn 950/975 procedures, for example, close the assembly outlet isolation valve during downstream blowout and return it to the specified part-open position afterwards. These examples do not establish the procedure for another model. Use your model’s full sequence, not a final storage position during air flow.

    Stop air and relieve pressure before changing the setup. Backflow manuals commonly specify about 45° for ball valves after the required drainage and air work. Follow the model’s positions for each valve and test cock; the main supply stays closed.

  4. Step 4

    Check every required drain path and retained-water space

    Test cocks alone do not prove complete drainage. FEBCO 765 and 850/860 instructions also address inlet/outlet drain paths; the 850/860 procedure includes model-specific internal handling. Relief-port flow on an RPZ does not prove every chamber is empty. Follow the exact manual or qualified service, including risers and connecting pipe.

  5. Step 5

    Use only the model’s internal-service instructions

    PVB bonnet or poppet removal is not universal, and merely loosening a bonnet does not prove drainage. Different DC/RP assemblies also have different cover and internal procedures. Do not disassemble from a generic device-family guide; use the manufacturer’s service instructions and any required testing before return to use.

  6. Step 6

    Complete the specified freeze protection and final storage

    Removal, draining, insulation or a heated enclosure must suit the actual model and installation. Union fittings alone are not instructions to remove a device. After any air work is stopped and pressure relieved, complete drainage and set the specified storage positions; keep the upstream water supply closed. Confirm any required reassembly and retesting with qualified backflow service.

    Insulation alone does not establish that retained water is protected through a sustained freeze.

What “45°” looks like from above

Water can be trapped between a backflow ball valve’s ball and body with the valve fully open or fully closed. A half-open position can provide a drainage path where the manufacturer specifies it. These are representative schematics, not proof that a particular assembly is drained or permission to leave an air-isolation valve half open during blowout.

  • Ball valve fully open; water can remain between the ball and bodyThe bore aligns with the pipe. The highlighted space around the ball represents a cavity that can retain water even with the valve fully open.

    Open — normal service

    Open flow through the bore does not prove the cavity between the ball and body is drained.

  • Ball valve half open at 45 degrees; drainage is unverifiedThe dashed highlighted cavity may still contain water. A half-open position can open a drainage path where the model specifies it, but the angle alone does not establish that the installation is drained.Drainage unverified

    45° — specified storage position

    Where the manual specifies 45°, use it for drainage and final storage after air is off and pressure relieved. Air-phase isolation is a different setting.

  • Ball valve fully closed; water can remain between the ball and bodyThe bore turns across the pipe. The highlighted cavity between the ball and body can hold water; fully closed and fully open positions can both trap it.

    Closed — isolation, not proof of drainage

    A closed valve may be required to isolate air or water during work. Afterwards, follow the model’s drainage and storage instructions; the water supply shutoff stays closed.

Device by device

PVB

Pressure Vacuum BreakerAbove ground
Pressure vacuum breaker (PVB)A single body above ground on two risers, with a domed bonnet on top, two test cocks, and an isolation ball valve on each riser.

A PVB is a single brass body on a riser about a foot above the highest sprinkler head, with a domed bonnet on top, two ball valves below it, and two small test cocks on the side. The most common device on residential irrigation in freeze country.

Drain it like this

  1. Identify the PVB manufacturer and model and obtain its freeze-protection instructions. If the model or drain arrangement is unknown, use a qualified backflow professional before opening parts or connecting air.
  2. Follow the PVB manual to shut off the water supply, relieve pressure and drain the assembly and both risers. The two test cocks alone may not drain every chamber.
  3. Bonnet or poppet removal is model-dependent. Do not loosen or remove internals on the strength of this drawing; follow the specified service and retest requirements.
  4. If the downstream piping is blown out, establish the manual’s air-phase isolation first. A downstream connection alone does not isolate the device.
  5. After air is shut off, pressure is relieved and drainage is complete, set the isolation valves and test cocks to the manual’s storage positions. Many specified ball valves use 45° at this final stage; the upstream water shutoff stays closed.

The mistake to avoid: Water retained between a ball and its valve body can freeze in either the fully open or fully closed position. Follow the exact model’s drainage and final storage directions; the outlet isolation setting during air work is a separate step.

RPZ

Reduced Pressure Zone assemblyAbove ground
Reduced pressure zone assembly (RPZ)A larger above-ground body with four test cocks and a relief valve hanging underneath that periodically discharges water to the ground.

An RPZ is the big one: two check valves in line with a relief valve hanging underneath that occasionally dumps water on the ground. Required where the system carries fertilizer injection or a higher hazard rating, and usually the most expensive device on the property.

Drain it like this

  1. Find the exact RPZ model and its freeze-protection procedure. Unknown models or drain paths need qualified backflow service before disassembly or air use.
  2. Follow the RPZ manual to shut off supply, relieve pressure and drain the body, risers and connecting pipe. The four test cocks and relief-port discharge do not establish that every internal chamber is empty.
  3. Internal check or relief-cover handling varies by model. Do not use a generic cover-loosening or removal procedure.
  4. For downstream blowout, isolate the assembly as the manual requires during air flow. Only after air is off and pressure relieved should final drainage and storage positions be completed. Ball valves commonly use about 45° for storage; follow the model for every valve and test cock, keeping the main supply closed.
  5. Follow the manufacturer’s freeze-protection and any service/retest requirements. Insulation alone does not establish that retained water is protected.

The mistake to avoid: Wrapping an RPZ assembly in insulation without draining it first. Insulation slows a freeze down; it does not prevent one, and a full assembly will still split in a sustained hard freeze.

DC

Double Check valve assemblyUsually below grade
Double check valve assembly (DC)Two check valves in one body with four test cocks and no relief valve underneath, usually installed below grade inside a valve box.

A double check is two check valves in a single body with four test cocks and no relief valve underneath. Often installed below grade in a valve box, which is what makes it the least freeze-prone of the four.

Drain it like this

  1. Identify the exact double-check model and installation. If either is unknown, arrange qualified backflow service before opening parts or connecting air.
  2. Follow the double-check instructions to shut off supply, relieve pressure and drain the body, risers and connecting pipe. The four test cocks alone may leave water trapped inside.
  3. Use the model’s required drain paths and internal service procedure; another double-check model’s cover instructions are not interchangeable.
  4. Keep the manual’s air-phase isolation distinct from its final valve-storage positions. Complete final drainage and storage only after compressed air is stopped and pressure relieved. Ball valves commonly use about 45° for storage; follow the model for every valve and test cock, keeping the main supply closed.
  5. A double check in a below-grade box can still freeze, and the box does not prove the device has drained.

The mistake to avoid: Assuming a below-grade device is safe by definition. It is safer, not safe: a box under a cleared driveway with no snow cover freezes surprisingly deep.

AVB

Atmospheric Vacuum BreakerAbove ground
Atmospheric vacuum breaker (AVB)A small single body on a riser downstream of a zone valve, with no test cocks and no isolation valves — it drains through the zone piping instead.

An AVB is the small, simple one — a single brass or plastic body downstream of each valve, with no test cocks and no isolation valves. Usually one per zone rather than one for the system.

Drain it like this

  1. Identify the AVB model and the zone’s approved winterization procedure; if unknown, use qualified help before applying air or opening components.
  2. A per-zone AVB has no test cocks or isolation valves in this representative arrangement. Colorado State Extension describes clearing it with its zone, while some general guides prohibit air through backflow devices. Verify the exact AVB and zone-valve instructions; do not apply a mainline assembly’s isolation sequence or assume every AVB permits air.
  3. Use the model-specific procedure for the valve, riser and downstream piping. Whether air is permitted depends on that equipment and installation.

The mistake to avoid: Looking for test cocks that do not exist and concluding the device has been dealt with. An AVB is only as drained as the zone it sits on.

When does your first freeze usually arrive?

The right sprinkler winterization method depends on your equipment, and the planning window depends on your location. Enter your ZIP for the NOAA freeze normals of the station we match to it — free, no signup required.

Free · no signup · NOAA 1991–2020 normals

Where this job usually trips people up

Do I really have to leave the ball valves at 45°?
Many specified backflow ball valves use 45° for drainage and final winter storage because water can be trapped between the ball and body when fully open or fully closed. Follow the actual model’s instructions. Temporary isolation during air work and the closed upstream water supply are separate requirements.
Should I take the backflow preventer off for winter?
Remove a backflow preventer for winter only if its manufacturer and installation instructions call for or permit that method. Confirm safe shutoff, pressure relief, storage, reassembly and any required retesting with qualified backflow service; unions alone do not establish a complete procedure.
Can I blow air through the backflow preventer?
Do not blow air through a backflow preventer unless the exact manufacturer procedure expressly permits it for your model and installation. Many procedures use an isolated downstream connection; downstream alone does not provide isolation. Watts 800M4 instructions describe a model-specific air purge, which is not permission to use it on another assembly. If unsure, use qualified backflow service.
Mine is below ground in a box — is it safe?
A backflow assembly in a below-grade box can still freeze, and being below grade does not establish that the assembly, risers or valve cavities have drained. Identify the model and installed drain paths and follow its freeze-protection procedure; do not apply another assembly’s instructions simply because both are double checks.

Get the reminder without scrolling back up

Enter your ZIP and we’ll set up the same reminder the ZIP tool higher on this page offers, timed to when it actually matters for your area.

Free · no signup · NOAA 1991–2020 normals

Check the instructions for your equipment

The equipment-manufacturer guides below explain the differences discussed here. Use the current instructions for your exact model, size and installation; an example for another device is not a procedure for yours. If you cannot verify them, use qualified service before connecting air or opening parts.

Where this guidance comes from

The university extension and public-agency publications listed here back specific statements on this page. Each publication says which statement it backs, so you can check the statement rather than take it on trust. Where a product label or your local extension office disagrees with anything here, follow the label or the extension office.

Don't rely on remembering

YardLedger offers general irrigation guidance, a record of your work and alerts for forecast freeze risk when your location, season and notification settings qualify. Mapped names help locate equipment; they do not verify a model-specific procedure. Confirm the installation with its manuals or qualified service, and check local conditions yourself.

Get my freeze reminder

Free to start • No credit card required.

Aerial satellite view of a property with three color-coded lawn zones drawn on the map, showing calculated area in square feet